09/11/2014 28 NI401
Gas Furnace CFM
See previous page on gas furnace hookup for proper programming of ECM motor for the required CFM output.
Outdoor Temp (OT) Factory Default Settings
Default
ST target temp 90° F (32° C)
Dead compressor ST 70° F (21° C)
OT temp, heating – HI > 20° F (-6° C)
OT temp, cooling – HI > 90° F (32° C)
EZGEO Board Dial Configurations
Below is a list of different configurations the EZGEO system can be adapted to and the matching appropriate
EZGEO board settings.
Heat pump only
• Mode Dial: A
• SW Over Dial: 0
• AUX EL: 0
• SOT Dial: 0=30min 1=90min 2=180min 3=270min
• Thermostat type: Conventional 1H/2C
Undersized heat pump with electric heat package
• Mode Dial: B
• SW Over Dial: 0
• AUX EL: 1=(-30°F) 2=(-20°F) 3=(-10°F) 4=0°F 5=5°F 6=10°F
• SOT Dial 0=30min 1=90min 2=180min 3=270min
• Thermostat type: Conventional 1H/2C/E
Heat pump with emergency electric heat package
• Mode Dial: B
• SW Over Dial: 0
• AUX EL: 0
• SOT Dial: 0=30min/ 1=90min/ 2=180min/ 3=270min
• Thermostat type: Conventional 2H/2C
Undersized heat pump with electric heat package and fossil fuel furnace (for load control).
• Mode Dial: B
• SW Over Dial: 0
• AUX EL: 1=-30°F 2=-20°F 3=-10°F 4=0°F 5=5°F 6=10°F
• SOT Dial: 0=30min 1=90min 2=180min 3=270min
• Thermostat type: Conventional 1H/2C/E
Geothermal heat pump with electric heat package and fossil fuel furnace (for load control).
• Mode Dial: B
• SW Over Dial: 0
• AUX EL: 0
• SOT Dial: 0=30min 1=90min 2=180min 3=270min
• Thermostat type: Conventional 2H/2C