09/11/2014 34 NI401
Unit Operating Conditions – Cool
Model
Source
Temp
Source
temp ∆
GPM
Air temp Δ
Dry bulb
Amps 240
Blower
AMPS
Nominal CFM
Discharge
80 deg A-
RT
Discharge
temp
TXV
Suction
bulb
Suction
temp at
bulb
at bulb
50 8.5-10.5 10 20-25 7.6-9.6 2.1 1210-1250 197-217 109-115 4.6-8.6
119-129
55-61 14.5-18.5
124-134
127-137
86 6.8-8.8 10 20-25 11.7-13.7 2.2 1230-1270 324-344 149-155 8.3-12.3
55-61 12.1-16.1
50 11.6-13.6 12 22-27 7.2-9.2 3.3 1670-1710 223-243 110-116 6.3-10.3
130-140
57-63 12.0-16.0
131-141
133-143
86 10.0-12.0 12 20-25 17.0-19.0 3.3 1680-1720 350-370 144-150 8.8-12.8
59-65 11.2-15.2
50 10.4-12.4 15 20-25 14.2-16.2 5.1 2010-2050 219-239 122-128 7.0-11.0
129-139
64-70 19.4-23.4
133-143
137-147
86 8.8-10.8 15 17-22 20.4-22.4 5.2 2050-2090 342-362 156-162 7.2-11.2
138-148
68-74 18.8-22.8
50 9.0-12.0 18 22-27 18.8-20.8 4.8 2200-2240 221-241 142-148 5.0-9.0
111-121
66-72 29.6-33.6
116-126
123-133
86 9.0-11.0 18 20-25 25.7-27.7 4.9 2200-2240 352-372 160-166 7.4-11.4
64-70 20.5-24.5
RA-VE-061
RA-VE-073
RA-VE-041
RA-VE-053
Comentários a estes Manuais