09/11/2014 33 NI401
Unit Operating Conditions – Heat
Model
Source
Temp
Source
temp Δ
GPM Air temp Δ Amps 240
Blower
AMPS
CFM
Discharge
pressure at 68
deg A-RT
Discharge
temp
Sub cool at
TXV
Suction
pressure at
bulb
Suction
temp at
bulb
Super-
heat at
bulb
32 3.4-5.4 10 25-30 11.2-13.2 1.9 1170-1210 305-325 160-166 10.4-14.4 77-87 29-35 10-14
50
5.7-7.7
10
32-37
12.4-14.4
2.0
1170-1210
351-371
160-166
11.9-15.9
111-121
46-52
9-13
68 8.4-10.4 10 39-44 13.7-15.7 2.0 1200-1250 395-415 161-167 11.3-15.3 145-155 62-68 10-14
32 3.9-5.9 12 25-30 16.4-18.4 3.2 1590-1630 317-337 158-164 8.2-12.2 75-85 29-35 11-15
50
6.4-8.4
12
32-37
18.0-20.0
3.3
1590-1630
358-378
155-161
11.6-15.6
106-116
44-50
9-13
68 9.2-11.2 12 39-44 19.7-21.7 3.2 1530-1570 402-422 153-159 12.2-16.2 139-149 57-63 8-12
32 3.0-5.0 15 26-31 18.9-20.9 3.8 1750-1790 313-333 168-174 8.5-12.5 75-85 31-37 13-17
50
7.5-9.8
15
32-37
20.7-22.7
3.9
1780-1820
351-371
166-172
11.5-14.5
102-112
45-51
12-16
68 7.8-9.8 15 40-45 22.8-24.8 4.0 1790-1830 400-420 167-173 10.8-14.8 140-150 60-66 11-15
32 3.5-5.5 18 28-33 23.8-25.8 4.5 2210-2250 335-355 162-168 14.2-18.2 73-83 28-34 11-15
50
5.6-7.6
18
35-40
26.8-28.8
4.4
2210-2250
380-400
161-167
14.5-18.5
99-119
42-48
8-13
68 8.1-10.1 18 42-47 29.9-31.9 4.5 2220-2260 432-452 164-170 12.1-16.1 142-152 57-63 7-11